Place of Origin |
Shanghai China (Mainland) |
we can design this load bank according to the customer requirements. LGFZL-1000 Load Bank SpecificationMain parameters and fitting 1Resistance load equipment: 1000KW 2Power factor: 1.0 3Test voltage: three phase AC voltage 400V 4Frequency: 50--60Hz 5Active power step: 5KW X 1 step 10KW X 1step 20KW X 2step 50KW X 1step 100KW X 1step 200KW X 4step 6Normal Operational Conditions In summer the ambient temperature is 45,humidity is 90%.In winter the ambient temperature is -20, humidity is 50% 7ventilation power and the control power of the load bank are 3 phase 5 wire ( 400V/50HZ). 8Cooling mode: forced air convection, the fanner with axial-flow, the direction of the air is coming from the bottom and outgoing from the above. 9Controlling mode: Manual control(computer can be selected). 10Load bank rated power error: thermal state: ±10, cold state: -2. 11Protection device: over-current, short-current, over-load protection for the fanner. With emergency stop, with circuit breaker for each branch of line incoming and load bank. 12Weight: 1500KG Main units 1) resistance material: stainless steel 304. 2) Circuit breaker: NS series of Schneider Cable specification: AGRP type withstand high temperature feature. Contactor: LC1 series contactor of Schneider. 3) the fanner with axial-flow 4)instrument: ETAS instrument RS-485 5)Transformer: ALH-0.66 of Changjiang of Jiangyin city 6) key: Changjiang of Jiangyin city 7) the frame is weld by material. 8)overall dimension: L2400 X W1100 X H1500