Place of Origin |
Fujian China (Mainland) |
Brand Name |
PHENIX |
Model Number |
184011 |
CE and UL approved universal emergencymodule 1. For emergency operation of Fluorescent lamps. For normal operation must be used a separate AC ballast. See instruction manual for further details 2. Start up time of normal operation is max. 5 seconds, also at low battery level. Start up time of emergency operation is max. 0.5 seconds 3. A LED signal lamp is lit when the module is in normal operation and is switched off when the lamp is in emergency operation 4. At normal surrounding temperature (from 0 Cº to 40 Cº), the charging time of the battery pack from 0%- to 100% is max. 24 hours. The discharging time is min.90 minutes 5. Emergency operate one lamp minimum 90 minutes at reduced light output 6. Battery pack is integrated with the emergency module. 7. Installation according to the instruction manual. Mains supply120V to 277V, 50/60HzTolerance of mains supply100-300VInput Wattage3.5WMax. Input current0.05AMax. Charging current110mABattery Rating1.5Ah 12V (1.2V x 10PCS) Nicd battery SC type, 18WHLamps operatedMost T5, T8, circular, compact fluorescent lampsEmergency operation (if 18W lamp is installed)min 180 minutes.Charging cycles*min 500.Life time for battery pack5 yearsOperation time for module*30,000 hoursSwitching cycles for module*20,000 timesLife time of module*5 yearsCompliant standardsEN55015; EN61000-3-2; EN61000-3-3; EN61547; EN61347-1; EN61347-2-7; EN61347-1.ApprovalCE/EMC and CE/LVD approval by TUV RheinlandMounting Measurement:L149.6(140)x48.8x30.5mm* At normal surrounding temperatures (from 0 Cº to 40 Cº)