Place of Origin |
Zhejiang China (Mainland) |
Brand Name |
CSR |
Model Number |
NA150-P |
150A battery sensor Applications: For the electronic measurement of currents: AC, DC IMPL.,etc.,with galvanic isolation between the primary (high power) and the secondary (electronic) circuits. Main technical data: 1. Primary normal current IPN: 150A r.m.s 2. Primary current, measuring range IP: 0 +/-200A 3. Measuring resistance: RMmin RMmax with +/-15V @ +/-200A max: 0 ohm 15 ohm 4. Secondary normal current: 75mA rms 5. Conversion ratio: 1:2000 6. Supply voltage(+/-5%): +/-15V 7. Current consumption: 16mA+ Secondary output current 8. Isolation test: Between the primary circuit to the secondary circuit(+.-.M):2.5kVrms/50Hz/1min Accuracy – Dynamic performance data: 1. Accuracy @ IPN, TA=+25 oC , @+/-15V: +/-1% 2. Non-linearity: better than +/-0.25% 3. Offset current Io: not more than +/-0.2mA(@+25oC) 4. Residual current @ IP=0, TA=+25 oC, after an overload of 1xIP: +/-0.15mA 5. Thermal drift of Io: +/-0.005mA/K 6. Response time: not more than 1us 7. dI/dt accurately followed: better than 200A/us 8. Frequency Bandwidth (-1dB): DC 0..150kHz General data: 1. Operating temperature: -10ºC +80ºC 2. Storage temperature: -15 oC +85 oC 3. Secondary coil resistance: not more than 120 ohm 4. Weight: 25g 5. Standards: EN 50178 Features: 1. Hall effect measuring principle 2. Galvanic isolation between primary and secondary circuit 3. Insulated plastic case made of white PPO recognized according to UL 94-V0 4. The whole current transducer comply with RoHS Directive completely