出生地 |
Beijing China (Mainland) |
牌子的名字 |
Tongdy |
模式的数量 |
MO39011 |
Gas detected Ozone Sensing element Semiconductor ozone gas sensor Power Supply 24VAC/VDC Consumption 0.25W Warm up time 96 hours (first time) 1 hour(operational) Signal Update 2s O3 Measuring Range 10 1000ppb Output One on/off resource output with 1A.Default setpoint: 80ppbCommunication rate RS485 with 19200bps rateControl mode Increase ozone level or decrease ozone level selectable by RS485 interfaceThe set point which control the output can be preset by the RS485 interfaceOperation temperature 050 (32122)Operation humidity 095%RH, non condensing Storage conditions -4070 (-40158) Weight 80g Dimensions 113mm×Æ16.5mm Housing/ IP rate PC/ABS plastic fireproof material, IP30 Quality System ISO 9001 1.Convenient mounting way as will , real time detect ozone with measuring range 10 1000ppb. 2.Semiconductor ozone gas sensor inside with more than 5 years lifetime. 3.The one resource on/off output to control a fan or an ozone generator/disinfector. 4.RS-485 communication interface can be used to preset the ozone set point and control mode, also used to zero calibrate as necessary 5.Smart structure design to make its mounting conveniently and easilyfor more application.