出生地 |
Japan |
牌子的名字 |
YOKOGAWA |
模式的数量 |
bt200 BRAIN Terminal |
The BT200 BRAIN Terminal is used to set, change, display and print out parameters such as tag numbers, output mode, and range for equipment that use BRAIN communications. This handheld terminal also monitors I/O values and self-check results, sets constant-current output, and allows zero adjustments. To perform these functions, it must be connected to the equipment’s 4 to 20mA DC signal transmission lines or to a dedicated connector on the ESC (Signal Conditioner Communication Card) when the system is started up or maintained. Features: BT200 BRAIN Terminal Online non-interruptive (transparent) communication The modulated communication signal does not interrupt the 4 to 20 mA DC signals on the communications loop. This loop functions automatically while the terminal is online. Diagnostics/ security with error messages In addition to the terminal’s self-check functions, there is a code entry function that helps maintain the integrity of important setup data. Built-in thermal printer This option enables on-the-spot printouts of tag numbers, calibrations, configurations, and more. Customers will appreciate the ability to print out quality assurance and ISO 9000 documentation.