出生地 |
Fujian China (Mainland) |
牌子的名字 |
CEE |
模式的数量 |
CEE ZJTLS |
Straight Joints Type ZJTLS Up to 36 kV Application For jointing copper wire screened or copper tape screened three-cores or single-core cable to be laid in air or directly buried. Table 16 Table XCable insulation rangeUse for8.7/15 kV jointCableInsulationCodeCable InsulationRangeCable Cross SectionInchesmmmm2A.67 .7917.0 20.025,35,50B.79 .9820.0 25.070,95,120C.98 1.1825.0 30.0150,185,240D1.18 1.4230.0 36.0300,400E1.42 1.5036.0 38.0500Table 17 Table XCable insulation rangeUse for12/20 kV jointCableInsulationCodeCable InsulationRangeCable Cross SectionInchesmmmm2A.79 .9820.0 25.035,50,70B.98 1.1825.0 30.095,120,150C1.18 1.4230.0 36.0185,240,300D1.42 1.5036.0 38.0400,500Table 18 Table XCable insulation rangeUse for18/30 kV joint19/33 kV jointCableInsulationCodeCable InsulationRangeCable Cross SectionInchesmmmm2A.95 1.0624.0 27.035B1.02 1.3426.0 34.050 70C1.18 1.5830.0 40.095 185D1.54 1.7739.0 45.0240 300E1.73 2.0144.0 51.0400 500Example: A joint is required for a 8.7/15kV, 300mm2 compacted, three core copper tape screen cable with a diameter over core insulation of 30.6mm. Order a ZJTLS15-300/3 –DT joint.