Место происхождения |
Zhejiang China (Mainland) |
Бренд |
FDTRADE |
Номер Модели |
Earth Leakage |
Тип |
Остаточный ток |
Notice: The following picture is 3KA RCBO, its principle is same as 6KA RCBO. Scope of application DL7NL-40 earth leakage circuit breakers are mainly applied to the AC 50Hz/60Hz circuit rated 240V and 40A or below, They have the electric leakage (electric shock), overload, short circuit and so on protection functions. The over voltage protection function can also be provided upon requirements. They are mainly used to protect the building illumination and power distribution system. Specifications Rated Voltage (V) Rated Current (A) In (mA)In o (mA) Break time Icn, Ics Im (A)I 2 In 0.25A 500A 240 6,10,16,20,25, 32,40 30,100 15,50 ≤0.1 ≤0.05 ≤0.04 ≤0.04 6kA 2000 Main Technical Parameters Testing Current Rated Current(A) Initial state Testing Time ( T ) Testing Result Note 6,10,16,20,25,32,401.13In Cold State ≥1h Not Tripped 1.45In Thermal State <1h Tripped Current stably rise to specified value in 5s. 2.55In Cold State 1-60s Tripped Tripper TypeB3In Cold State ≥0.1s Not Tripped 5In Cold State <0.1s Tripped C5In Cold State ≥0.1s Not Tripped 10In Cold State <0.1s Tripped D10In Cold State ≥0.1s Not Tripped 50In Cold State <0.1s Tripped Installation and the wiring diagram Install breaker Take down breaker Push down the DIN rail, installing the cardTilt over the device and raise it upNote: It will be locked when you pull out the rail installing card, so, before installing the device onto the DIN rail again, you should push it inward. Combined with the other same type product The advantage of DL7NL-40: it takes double modulus The advantage of DL7NL-40: breaking capability is 6kA